Description:
ELEC RECONNECT

Outstanding Activity Conditions

Permit Number - T06EL00629
Permit Status: Expired
Permit Description: ELEC RECONNECT
Total Outstanding Activity Conditions - 1
Date Name
04/04/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T06EL00629
Permite Description: ELEC RECONNECT
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
04/05/2006 ELECTRIC - RECONNECT N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/05/2006 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. THE CONDUCTORS IN THE MAIN DISCONNECT AT TERMINATIONS ARE CORRODED AND SHOW SIGNS OF DISCOLORATION.
2. THE NEUTRAL HAS BEEN SHORTED OUT AND SEVERAL STRANDS BURNED OFF.
3. SE CABLE COMING INTO BACK OF DISCONNECT NEEDS A BUSHING TO PROTECT IT AGAINST METAL.
4. TERMINALS ON KNIFE HANDLE AND SWITCH BLADES AND BLADE ENCLOSURE IN NEED OF BEING CLEANED DUE TO OLD AGE OF 30 AMP MAIN DISCONNECT SUGGEST YOU UP GRADE THIS SERVICE.
5. GROUND WIRES TO BE TIED OR SUPPORTED TO WALL.
6. THIS HOUSE IS WIRED WITH AN UNGROUNDED SYSTEM, ALL RECEPTACLES ARE TO BE OF 2 WIRE 2 HOLE TYPE.
7. FUSE BOX IN KITCHEN - NEEDS TO BE UPGRADED FUSE BLOCK NO LONGER ATTAINED TO ENCLOSURE, CONDUCTORS OVER FUSED, TERMINATIONS NEED TO BE RECORRECTED.
8. COOLER BOXES TO BE WEATHERPROOF.
9. IF STORAGE ROOM HAS ELECTRICAL -
HAVE OPEN NEXT INSP.