Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THE CONDUCTORS IN THE MAIN DISCONNECT AT TERMINATIONS ARE CORRODED AND SHOW SIGNS OF DISCOLORATION. 2. THE NEUTRAL HAS BEEN SHORTED OUT AND SEVERAL STRANDS BURNED OFF. 3. SE CABLE COMING INTO BACK OF DISCONNECT NEEDS A BUSHING TO PROTECT IT AGAINST METAL. 4. TERMINALS ON KNIFE HANDLE AND SWITCH BLADES AND BLADE ENCLOSURE IN NEED OF BEING CLEANED DUE TO OLD AGE OF 30 AMP MAIN DISCONNECT SUGGEST YOU UP GRADE THIS SERVICE. 5. GROUND WIRES TO BE TIED OR SUPPORTED TO WALL. 6. THIS HOUSE IS WIRED WITH AN UNGROUNDED SYSTEM, ALL RECEPTACLES ARE TO BE OF 2 WIRE 2 HOLE TYPE. 7. FUSE BOX IN KITCHEN - NEEDS TO BE UPGRADED FUSE BLOCK NO LONGER ATTAINED TO ENCLOSURE, CONDUCTORS OVER FUSED, TERMINATIONS NEED TO BE RECORRECTED. 8. COOLER BOXES TO BE WEATHERPROOF. 9. IF STORAGE ROOM HAS ELECTRICAL - HAVE OPEN NEXT INSP. |