Permit Details

Status:
Expired
Type:
MULTI FAMILY OTHER
Address NEW:
2832 N EUCLID AV #01
Apply Date:
02/21/2006
Applicant:
CUSTOM ELECTRICAL SOLUTIONS
Description:
REPLACE:ELECTRIC BOX (4) METERS
Contractors:
  • CUSTOM ELECTRICAL SOLUTIONS

Permit Reviews

Permit Number - T06EL00337
Permit Status: Expired
Permit Description: REPLACE:ELECTRIC BOX (4) METERS
Start Date Submittal Complete Date Status  
02/21/2006 ELECTRICAL 02/21/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06EL00337
Permit Status: Expired
Permit Description: REPLACE:ELECTRIC BOX (4) METERS
Total Outstanding Activity Conditions - 1
Date Name
02/21/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T06EL00337
Permite Description: REPLACE:ELECTRIC BOX (4) METERS
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
02/23/2006 ELECTRIC - UNDERGROUND N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/23/2006 ELECTRIC - INTERMEDIATE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/23/2006 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GAS PIPE BONDED ON WRONG END OF METER - MUST BE ON CUSTOMER SIDE
2. STRAP #2 BARE TO WALL BELOW SERVICE.
3. BOND GROUNDING ELECTRODE CONDUCTOR TO NEUTRAL BAR OR INSTALL MAIN BONDING JUMPER PER 250 NEC WHEN USING MECH. LUG TO ENCLOSURE YOU MUST SCRAPE OFF ENAMEL & USE BOLT & NUT, SELF TAPPING SCREWS NOT ALLOWED PER 250 NEC