Permit: T06EL00337

Parcel: 11308227C

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/23/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GAS PIPE BONDED ON WRONG END OF METER - MUST BE ON CUSTOMER SIDE
2. STRAP #2 BARE TO WALL BELOW SERVICE.
3. BOND GROUNDING ELECTRODE CONDUCTOR TO NEUTRAL BAR OR INSTALL MAIN BONDING JUMPER PER 250 NEC WHEN USING MECH. LUG TO ENCLOSURE YOU MUST SCRAPE OFF ENAMEL & USE BOLT & NUT, SELF TAPPING SCREWS NOT ALLOWED PER 250 NEC