Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GAS PIPE BONDED ON WRONG END OF METER - MUST BE ON CUSTOMER SIDE 2. STRAP #2 BARE TO WALL BELOW SERVICE. 3. BOND GROUNDING ELECTRODE CONDUCTOR TO NEUTRAL BAR OR INSTALL MAIN BONDING JUMPER PER 250 NEC WHEN USING MECH. LUG TO ENCLOSURE YOU MUST SCRAPE OFF ENAMEL & USE BOLT & NUT, SELF TAPPING SCREWS NOT ALLOWED PER 250 NEC |