Permit Details

Status:
Withdrwn
Type:
SINGLE FAMILY OTHER
Address NEW:
1140 E ADELAIDE DR
Apply Date:
02/09/2006
Applicant:
CASCADE ELECTRIC INC *C
Description:
REPLACE: 200A SVC (APA)
Contractors:
  • CASCADE ELECTRIC INC *C

Outstanding Activity Conditions

Permit Number - T06EL00274
Permit Status: Withdrwn
Permit Description: REPLACE: 200A SVC (APA)
Total Outstanding Activity Conditions - 1
Date Name
02/09/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Withdrwn
Permit Number: T06EL00274
Permite Description: REPLACE: 200A SVC (APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
03/28/2006 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FINISH MARKING PANEL SCHEDULE AT SERVICE
2. EFFECTIVELY CLOSE OF OPENING WHERE #4 BARE COPPER ENTERS BOTTOM OF SERVICE.
3. DOUBLE POLE 30 AMP CB ON CIRCUITS 5 & 7 BROKEN - REPLACE.
4. PVC BELOW SERVICE NEEDS TO BE BURIED 18" BELOW GRADE.
5. GROUNDING ELECTRODE CONDUCTOR CANNOT BE SPLICED WITH A KEARNY - MUST BE OF AN IRREPRESIBLE TYPE.
6. WHRE IS MAIN DISCONNECT MEANS FOR HOUSE?

Completed Inspections

Permit Status: Withdrwn
Permit Number: T06EL00274
Permit Description: REPLACE: 200A SVC (APA)
Total Completed Inspections - 2
Date Description Inspector Results Comments
02/22/2006 ELECTRIC - INTERMEDIATE RMAJUTA Approved IVRS - Inspection :*OK TO CLEAR SERVICE INC
HOUSE BEING ITS OWN STRUCTURE MUST HAVE ITS OWN DISCONNECT ( THIS HAS ALWAYS BEEN REQUIRED
2ND GROUND ?? REQUIRED ( AT BASE OF SERVICE
AT CROSS OVER ID CIRCUITS
HOUSE ALSO TO HAVE ITS OWN GROUND SYSTEM
02/23/2006 TEP CLEARANCE - AM JKOZUCH Approved INC