Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FINISH MARKING PANEL SCHEDULE AT SERVICE 2. EFFECTIVELY CLOSE OF OPENING WHERE #4 BARE COPPER ENTERS BOTTOM OF SERVICE. 3. DOUBLE POLE 30 AMP CB ON CIRCUITS 5 & 7 BROKEN - REPLACE. 4. PVC BELOW SERVICE NEEDS TO BE BURIED 18" BELOW GRADE. 5. GROUNDING ELECTRODE CONDUCTOR CANNOT BE SPLICED WITH A KEARNY - MUST BE OF AN IRREPRESIBLE TYPE. 6. WHRE IS MAIN DISCONNECT MEANS FOR HOUSE? |