Permit: T06EL00224
Permit Details
Apply Date:
02/03/2006
Applicant:
MENDEZ FRANK G & LISA MARIE
Description:
UPGRADE:ELECTRIC 200AMP
Permit Reviews
Permit Number - T06EL00224
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 200AMP
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/03/2006 | ELECTRICAL | 02/03/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06EL00224
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 200AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 02/03/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06EL00224
Permite Description: UPGRADE:ELECTRIC 200AMP
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2006 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* THE SERVICE HAS NOT BEEN UPGRADED TO 200AMPS, IT HAS JUST HAD A PANEL CHANGED OUT. MAX HEIGHT TO TOP OF BREAKERS TO BE 6'7" ID BRANCH CKT'S NEUTRALS AND GROUNDS NEED TO BE SEPARATED PANEL ENCLOSURE NEED TO BE GROUNDED PROVIDE BUSHINGS FOR CONDUCTORS ENTERING ENCLOSURE MAX 15 AMP BREAKER FOR 14 GA WIRE INSTALL COVER FOR J-BOX NEXT TO PANEL |