Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/13/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* THE SERVICE HAS NOT BEEN UPGRADED TO 200AMPS, IT HAS JUST HAD A PANEL CHANGED OUT.
MAX HEIGHT TO TOP OF BREAKERS TO BE 6'7"
ID BRANCH CKT'S
NEUTRALS AND GROUNDS NEED TO BE SEPARATED
PANEL ENCLOSURE NEED TO BE GROUNDED
PROVIDE BUSHINGS FOR CONDUCTORS ENTERING ENCLOSURE
MAX 15 AMP BREAKER FOR 14 GA WIRE
INSTALL COVER FOR J-BOX NEXT TO PANEL