Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* THE SERVICE HAS NOT BEEN UPGRADED TO 200AMPS, IT HAS JUST HAD A PANEL CHANGED OUT. MAX HEIGHT TO TOP OF BREAKERS TO BE 6'7" ID BRANCH CKT'S NEUTRALS AND GROUNDS NEED TO BE SEPARATED PANEL ENCLOSURE NEED TO BE GROUNDED PROVIDE BUSHINGS FOR CONDUCTORS ENTERING ENCLOSURE MAX 15 AMP BREAKER FOR 14 GA WIRE INSTALL COVER FOR J-BOX NEXT TO PANEL |