Permit: T06EL00076
Permit Details
Apply Date:
01/17/2006
Applicant:
JENNIFER FINGER
Description:
ELEC UPGRADE 200AMPS
Permit Reviews
Permit Number - T06EL00076
Permit Status: Expired
Permit Description: ELEC UPGRADE 200AMPS
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/17/2006 | ELECTRICAL | 01/17/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06EL00076
Permit Status: Expired
Permit Description: ELEC UPGRADE 200AMPS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/17/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06EL00076
Permite Description: ELEC UPGRADE 200AMPS
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2006 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
| 02/02/2006 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* USE A #4 BOR BOND TO GAS & WATER 1. THE BOND & GROUND ROD WIRING TO ENTER CAN THRU A ROMEX CONNECTOR OR OTHER TO CLOSE HOLE. 2. THE SERVICE IS TO HAVE A LEVEL FLOORING BELOW IT AS TO NOT LET A TRIP HAZARD EXIST DRIVE GROUND RODS TO GRADE OR BELOW 3. TWO SUPPORTS ON RISER BELOW ROOF NO PLASTIC ANCHORS & MUST BE 1/4" SIZE 4. SEAL ROOF JACK TO ROOF 5. EQUIPMENT WIRE (GREEN) RUN IN SEAL TIGHT TO ATTACH TO GREEN SCREW IN J-BOX, RUN A WHITE #10 FROM PANEL TO TIE TO NEUTRAL IN J-BOX *NOTE: THIS SERVICE HAS BEEN ENERGIZED WITHOUT CITY APPROVAL! CORRECT AND RECALL ASAP |