Permit: T06EL00076

Parcel: 115011000


Addresses:

2224 N 3RD AV

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/02/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
USE A #4 BOR BOND TO GAS & WATER
1. THE BOND & GROUND ROD WIRING TO ENTER CAN THRU A ROMEX CONNECTOR OR OTHER TO CLOSE HOLE.
2. THE SERVICE IS TO HAVE A LEVEL FLOORING BELOW IT AS TO NOT LET A TRIP HAZARD EXIST DRIVE GROUND RODS TO GRADE OR BELOW
3. TWO SUPPORTS ON RISER BELOW ROOF NO PLASTIC ANCHORS & MUST BE 1/4" SIZE
4. SEAL ROOF JACK TO ROOF
5. EQUIPMENT WIRE (GREEN) RUN IN SEAL TIGHT TO ATTACH TO GREEN SCREW IN J-BOX, RUN A WHITE #10 FROM PANEL TO TIE TO NEUTRAL IN J-BOX
*NOTE: THIS SERVICE HAS BEEN ENERGIZED WITHOUT CITY APPROVAL! CORRECT AND RECALL ASAP