Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* USE A #4 BOR BOND TO GAS & WATER 1. THE BOND & GROUND ROD WIRING TO ENTER CAN THRU A ROMEX CONNECTOR OR OTHER TO CLOSE HOLE. 2. THE SERVICE IS TO HAVE A LEVEL FLOORING BELOW IT AS TO NOT LET A TRIP HAZARD EXIST DRIVE GROUND RODS TO GRADE OR BELOW 3. TWO SUPPORTS ON RISER BELOW ROOF NO PLASTIC ANCHORS & MUST BE 1/4" SIZE 4. SEAL ROOF JACK TO ROOF 5. EQUIPMENT WIRE (GREEN) RUN IN SEAL TIGHT TO ATTACH TO GREEN SCREW IN J-BOX, RUN A WHITE #10 FROM PANEL TO TIE TO NEUTRAL IN J-BOX *NOTE: THIS SERVICE HAS BEEN ENERGIZED WITHOUT CITY APPROVAL! CORRECT AND RECALL ASAP |