Description:
ELEC RECONNECT

Outstanding Activity Conditions

Permit Number - T06EL00010
Permit Status: Closed
Permit Description: ELEC RECONNECT
Total Outstanding Activity Conditions - 1
Date Name
01/04/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Closed
Permit Number: T06EL00010
Permite Description: ELEC RECONNECT
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
01/05/2006 ELECTRIC - RECONNECT N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
#1 SERVICE - IMPROPER SERVICE GROUNDING, IMPROPER WIRING METHODS, OPEN WIRING, MULTIPLE LUGGING, UNATTACHED WIRING SE CABLE GOING INTO BLDG W/O PROTECTION, IMPROPER OVER CURRENT PROTECTION.
#2 OUTSIDE COMPRESSOR - OPEN WIRING, OPEN RACEWAYS, MISSING COVERS, NORTH WALL OUTSIDE UNSUPPORTED WIRING & CONDUITS, OUTSIDE OPEN SPLICES TO LIGHTING.
#3 LIFT AREA - NON WEATHERPROOF WIRING DEVICES, OUTDOOR PANEL ON WALL NOT RATED FOR OUTSIDE.
#4 OUTDOOR SPRAY BOOTHS - OUTSIDE WIRING NOT WEATHERPROOF REMOVE OR CORRECT.
#5 ALL OUTSIDE LIGHTING TO BE WEATHERPROOF & LISTED FOR AREA
#6 EAST AREA OUTSIDE COMPRESSORS TO BE WIRED CORRECTLY
#7 ALL INSIDE LIGHTING TO BE WIRED CORRECTLY NO OPEN SPLICING - USE LIGHTING AT PROPER HEIGHTS - 12'
#8 REMOVE ROMEX IN SHOP AREA
TOO MANY ELECTRICAL VIOLATIONS - OBTAIN SERVICES OF ELECTRICAL CONTRACTOR TO CORRECT ELECTRICAL VIOLATIONS & RECALL FOR INSPECTION.

Completed Inspections

Permit Status: Closed
Permit Number: T06EL00010
Permit Description: ELEC RECONNECT
Total Completed Inspections - 2
Date Description Inspector Results Comments
03/03/2006 ELECTRIC - FINAL RMAJUTA Approved IVRS - Inspection :*
03/06/2006 TEP CLEARANCE - AM JWEATHER Approved OK TO CLEAR RECN PER R. MAJUTA