Permit: T06EL00010


Addresses:

101 E RILLITO ST

Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
01/05/2006 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
#1 SERVICE - IMPROPER SERVICE GROUNDING, IMPROPER WIRING METHODS, OPEN WIRING, MULTIPLE LUGGING, UNATTACHED WIRING SE CABLE GOING INTO BLDG W/O PROTECTION, IMPROPER OVER CURRENT PROTECTION.
#2 OUTSIDE COMPRESSOR - OPEN WIRING, OPEN RACEWAYS, MISSING COVERS, NORTH WALL OUTSIDE UNSUPPORTED WIRING & CONDUITS, OUTSIDE OPEN SPLICES TO LIGHTING.
#3 LIFT AREA - NON WEATHERPROOF WIRING DEVICES, OUTDOOR PANEL ON WALL NOT RATED FOR OUTSIDE.
#4 OUTDOOR SPRAY BOOTHS - OUTSIDE WIRING NOT WEATHERPROOF REMOVE OR CORRECT.
#5 ALL OUTSIDE LIGHTING TO BE WEATHERPROOF & LISTED FOR AREA
#6 EAST AREA OUTSIDE COMPRESSORS TO BE WIRED CORRECTLY
#7 ALL INSIDE LIGHTING TO BE WIRED CORRECTLY NO OPEN SPLICING - USE LIGHTING AT PROPER HEIGHTS - 12'
#8 REMOVE ROMEX IN SHOP AREA
TOO MANY ELECTRICAL VIOLATIONS - OBTAIN SERVICES OF ELECTRICAL CONTRACTOR TO CORRECT ELECTRICAL VIOLATIONS & RECALL FOR INSPECTION.