Permit Details

Status:
Final
Type:
COMMERCIAL ALTERATION
Apply Date:
12/27/2006
Applicant:
THE CACHITA LIMITED PARTNERSHIP
Description:
TI: FOR OFFICE
Contractors:
  • EPSTEIN FENTON L L C ,

Permit Reviews

Permit Number - T06CM06523
Permit Status: Final
Permit Description: TI: FOR OFFICE
Start Date Submittal Complete Date Status  
01/24/2007 RESUBMITTAL 01/31/2007 COMPLETED Review Details
12/27/2006 COMMERCIAL TI 01/19/2007 COMPLETED Review Details
12/28/2006 COMMERCIAL TI 01/24/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06CM06523
Permit Status: Final
Permit Description: TI: FOR OFFICE
Total Outstanding Activity Conditions - 1
Date Name
12/27/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T06CM06523
Permit Description: TI: FOR OFFICE
Total Completed Inspections - 20
Date Description Inspector Results Comments
02/09/2007 FRAMING LHANLY Approved IVRS - Inspection :*
02/09/2007 NPPO - FINAL ACONNOR Approved N/A
02/09/2007 LANDSCAPE - FINAL ACONNOR Approved N/A
02/09/2007 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
02/12/2007 RIGHT OF WAY - FINAL MOTERO Approved PER EMAIL
02/16/2007 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
03/05/2007 FIRE SPKLR - FINAL LTHOMAS Approved
03/05/2007 FIRE - FINAL LTHOMAS Approved
03/08/2007 ENGINEERING - FINAL MRUSSO Approved
03/12/2007 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
ON FINAL MARK UNIT DATA PLATES W/HEAT STRIPS INSTALLED AND FUSE ACCORDINGLY.
CONNECT ALL SENSORS.
PROVIDE AIR BALANCE REPORT.
03/14/2007 ELECTRIC - ABOVE CEILING CCLEMENS Approved IVRS - Inspection :*
1. SECURE EQUIPMENT TO WALL
PLASTIC ANCHORS PULLING OUT, NOT EFFECTIVE -- NEC 110.13
2. NEUTRAL NOT TO BE USED TO BOND METER BASE AND DISCONNECT ENCLOSURES.
THESE ENCLOSURES ARE ON THE LOAD SIDE OF SERVICE DISCONNECT - NEC 250.24 A5
INSTEAD, USE EQUIPMENT GROUNDING CONDUCTOR TO GROUND EQUIPMENT AND KEEP SEPARATE FROM NEUTRAL. CONNECT TO EQUIPMENT GROUND BAR IN GUTTER -- 250.142
03/14/2007 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
03/15/2007 ELECTRIC - TEMP POWER FOR TEST CCLEMENS Approved IVRS - Inspection :*
03/16/2007 TEP CLEARANCE - AM JWEATHER Approved TEC CLEARED FOR #120 PER C. CLEMENS
03/20/2007 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
03/20/2007 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :*
1. CLEAN EXCESS TRASH OUT OF FLOOR BOXES
2. PLEASE LABEL UNITS AS TO SUITE #'S

OK FINAL
03/20/2007 ELECTRIC - INTERMEDIATE RHOLLAND Approved
03/20/2007 ELECTRIC - UNDERGROUND RHOLLAND Approved IVRS - Inspection :*
03/20/2007 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection :*
03/21/2007 PERMIT FINALED BFLORES Approved

Documents

File Name Document Type  
None CERT OF OCC VIEW
None DOCUMENTS VIEW
6523-01-0001-01-ORIGINAL001.TIF CONSTRPLANS VIEW
6523-01-0001-01-ORIGINAL002.TIF CONSTRPLANS VIEW
6523-01-0001-01-ORIGINAL003.TIF CONSTRPLANS VIEW
6523-01-0001-01-ORIGINAL004.TIF CONSTRPLANS VIEW
6523-01-0001-01-ORIGINAL005.TIF CONSTRPLANS VIEW
6523-01-0001-01-ORIGINAL006.TIF CONSTRPLANS VIEW
6523-01-0001-01-ORIGINAL007.TIF CONSTRPLANS VIEW