Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM06523

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
03/14/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
1. SECURE EQUIPMENT TO WALL
PLASTIC ANCHORS PULLING OUT, NOT EFFECTIVE -- NEC 110.13
2. NEUTRAL NOT TO BE USED TO BOND METER BASE AND DISCONNECT ENCLOSURES.
THESE ENCLOSURES ARE ON THE LOAD SIDE OF SERVICE DISCONNECT - NEC 250.24 A5
INSTEAD, USE EQUIPMENT GROUNDING CONDUCTOR TO GROUND EQUIPMENT AND KEEP SEPARATE FROM NEUTRAL. CONNECT TO EQUIPMENT GROUND BAR IN GUTTER -- 250.142
03/12/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8
2. ATTACH FIXTURE WITH 4 SCREWS IF USING CORNERS
3. M/C CABLE TO TERMINATE NOT SLEEVED THROUGH CONDUIT PER MANUFACTURE
4. WE HAVE BOXES OVERFILLED.