Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM06523
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* 1. SECURE EQUIPMENT TO WALL PLASTIC ANCHORS PULLING OUT, NOT EFFECTIVE -- NEC 110.13 2. NEUTRAL NOT TO BE USED TO BOND METER BASE AND DISCONNECT ENCLOSURES. THESE ENCLOSURES ARE ON THE LOAD SIDE OF SERVICE DISCONNECT - NEC 250.24 A5 INSTEAD, USE EQUIPMENT GROUNDING CONDUCTOR TO GROUND EQUIPMENT AND KEEP SEPARATE FROM NEUTRAL. CONNECT TO EQUIPMENT GROUND BAR IN GUTTER -- 250.142 |
|