Permit Details

Status:
Expired
Type:
MULTI FAMILY ALTERATION
Apply Date:
09/14/2006
Applicant:
JACA DESIGN
Description:
REPAIRS:INTERIOR AND RECONNECT:ELECT R1 Add plumbing inspections
Contractors:
  • POOR BOYS GENERAL REMODELING INC

Permit Reviews

Permit Number - T06CM05018
Permit Status: Expired
Permit Description: REPAIRS:INTERIOR AND RECONNECT:ELECT R1 Add plumbing inspections
Start Date Submittal Complete Date Status  
09/14/2006 RESIDENTIAL BLDG/ZONING/ENGINE/NPPO 09/19/2006 COMPLETED Review Details
10/13/2006 REVISION - - 1ST 10/17/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06CM05018
Permit Status: Expired
Permit Description: REPAIRS:INTERIOR AND RECONNECT:ELECT R1 Add plumbing inspections
Total Outstanding Activity Conditions - 1
Date Name
09/14/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T06CM05018
Permite Description: REPAIRS:INTERIOR AND RECONNECT:ELECT R1 Add plumbing inspections
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
SHEET ROCK NAILING N/A Not Inspected
BUILDING - FINAL N/A Not Inspected
04/16/2007 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NO POWER TO DINING ROOM RECEPTACLES
2. NO POWER TO KITCHEN RECEPTACLES
3. CANNOT REMOVE PANEL COVER PAINTED & CAULKED TO WALL
4. LABEL CIRCUITS AT PANEL PER NEC 408.4
5. ALL KITCHEN COUNTER TOP RECEPTACLES TO BE GFI PROTECTED PER NEC 210.8
6. INSTALL BOX EXTENSION ON RECEPTACLE UNDER SINK PER NEC 314.20
7. LENGTH OF CORD TO CONNECT DISHWASHER TO BE 3FT TO 4FT PER NEC 422.16
8. GROUND ALL SWITCHES PER NEC 404.9
9. SWITCH FACEPLATES TO SEAT AGAINST FINISHED SURFACE PER NEC 404.9
10. SMOKE DETECTORS NOT INTERCONNECTED
11. INSTALL FAN COVER IN BATHROOM

Completed Inspections

Permit Status: Expired
Permit Number: T06CM05018
Permit Description: REPAIRS:INTERIOR AND RECONNECT:ELECT R1 Add plumbing inspections
Total Completed Inspections - 5
Date Description Inspector Results Comments
11/20/2006 PLUMBING - INTERMEDIATE RMYERS Approved OK TO COVER ALL AREAS
11/22/2006 ELECTRIC - INTERMEDIATE RMAJUTA Approved IVRS - Inspection :*
1) FOR YOUR NEXT INTERMEDIATE INSPECTIONS PLEASE PLACE THE SMOKE DETECTOR WHICH YOU ARE INSTALLING IN THE SMALL HALL OUT INTO THE LIVING ROOM, MAKE SURE IT'S 3' AWAY FROM SUPPLY OR RETURN AIR GRILL
02/16/2007 ELECTRIC - RECONNECT CCLEMENS Approved IVRS - Inspection :*
02/20/2007 TEP CLEARANCE - AM JWEATHER Approved RECN CLEARED FOR #239 PER C. CLEMENS
02/21/2007 PLUMBING - FINAL RRICH Approved IVRS - Inspection :*