Permit: T06CM05018
Permit Details
Apply Date:
09/14/2006
Applicant:
JACA DESIGN
Description:
REPAIRS:INTERIOR AND RECONNECT:ELECT R1 Add plumbing inspections
Contractors:
- POOR BOYS GENERAL REMODELING INC
Permit Reviews
Permit Number - T06CM05018
Permit Status: Expired
Permit Description: REPAIRS:INTERIOR AND RECONNECT:ELECT
R1 Add plumbing inspections
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
09/14/2006 | RESIDENTIAL BLDG/ZONING/ENGINE/NPPO | 09/19/2006 | COMPLETED |
10/13/2006 | REVISION - - 1ST | 10/17/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06CM05018
Permit Status: Expired
Permit Description: REPAIRS:INTERIOR AND RECONNECT:ELECT
R1 Add plumbing inspections
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
09/14/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06CM05018
Permite Description: REPAIRS:INTERIOR AND RECONNECT:ELECT
R1 Add plumbing inspections
Total Outstanding Inspections - 3
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
SHEET ROCK NAILING | N/A | Not Inspected | ||
BUILDING - FINAL | N/A | Not Inspected | ||
04/16/2007 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO POWER TO DINING ROOM RECEPTACLES 2. NO POWER TO KITCHEN RECEPTACLES 3. CANNOT REMOVE PANEL COVER PAINTED & CAULKED TO WALL 4. LABEL CIRCUITS AT PANEL PER NEC 408.4 5. ALL KITCHEN COUNTER TOP RECEPTACLES TO BE GFI PROTECTED PER NEC 210.8 6. INSTALL BOX EXTENSION ON RECEPTACLE UNDER SINK PER NEC 314.20 7. LENGTH OF CORD TO CONNECT DISHWASHER TO BE 3FT TO 4FT PER NEC 422.16 8. GROUND ALL SWITCHES PER NEC 404.9 9. SWITCH FACEPLATES TO SEAT AGAINST FINISHED SURFACE PER NEC 404.9 10. SMOKE DETECTORS NOT INTERCONNECTED 11. INSTALL FAN COVER IN BATHROOM |
Completed Inspections
Permit Status: Expired
Permit Number: T06CM05018
Permit Description: REPAIRS:INTERIOR AND RECONNECT:ELECT
R1 Add plumbing inspections
Total Completed Inspections - 5
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/20/2006 | PLUMBING - INTERMEDIATE | RMYERS | Approved | OK TO COVER ALL AREAS |
11/22/2006 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | IVRS - Inspection :* 1) FOR YOUR NEXT INTERMEDIATE INSPECTIONS PLEASE PLACE THE SMOKE DETECTOR WHICH YOU ARE INSTALLING IN THE SMALL HALL OUT INTO THE LIVING ROOM, MAKE SURE IT'S 3' AWAY FROM SUPPLY OR RETURN AIR GRILL |
02/16/2007 | ELECTRIC - RECONNECT | CCLEMENS | Approved | IVRS - Inspection :* |
02/20/2007 | TEP CLEARANCE - AM | JWEATHER | Approved | RECN CLEARED FOR #239 PER C. CLEMENS |
02/21/2007 | PLUMBING - FINAL | RRICH | Approved | IVRS - Inspection :* |