Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05018
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO POWER TO DINING ROOM RECEPTACLES 2. NO POWER TO KITCHEN RECEPTACLES 3. CANNOT REMOVE PANEL COVER PAINTED & CAULKED TO WALL 4. LABEL CIRCUITS AT PANEL PER NEC 408.4 5. ALL KITCHEN COUNTER TOP RECEPTACLES TO BE GFI PROTECTED PER NEC 210.8 6. INSTALL BOX EXTENSION ON RECEPTACLE UNDER SINK PER NEC 314.20 7. LENGTH OF CORD TO CONNECT DISHWASHER TO BE 3FT TO 4FT PER NEC 422.16 8. GROUND ALL SWITCHES PER NEC 404.9 9. SWITCH FACEPLATES TO SEAT AGAINST FINISHED SURFACE PER NEC 404.9 10. SMOKE DETECTORS NOT INTERCONNECTED 11. INSTALL FAN COVER IN BATHROOM |