Permit: T06CM04478
Permit Details
Apply Date:
08/07/2006
Applicant:
DARDAMONE CARMINE F & CARDAMONE LAWRENCE
Description:
INSTALL:A/C & HEATING:GAS LINE R-1 Elec upgrade 100amps AND 2 CIRCUITS
Contractors:
- MARTIN S HEATING AND COOLING *C
Permit Reviews
Permit Number - T06CM04478
Permit Status: Expired
Permit Description: INSTALL:A/C & HEATING:GAS LINE
R-1 Elec upgrade 100amps AND 2 CIRCUITS
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
08/07/2006 | OTHER | 08/08/2006 | COMPLETED |
08/09/2006 | OTHER | 08/10/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06CM04478
Permit Status: Expired
Permit Description: INSTALL:A/C & HEATING:GAS LINE
R-1 Elec upgrade 100amps AND 2 CIRCUITS
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
08/07/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06CM04478
Permite Description: INSTALL:A/C & HEATING:GAS LINE
R-1 Elec upgrade 100amps AND 2 CIRCUITS
Total Outstanding Inspections - 3
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
ELECTRIC - SERVICE UPGRADE | N/A | Not Inspected | ||
08/31/2006 | PLUMBING - GAS PRESSURE TEST | N/A | Partial Approval | IVRS - Inspection :* - NEW GAS LINE - METER UP WALL TO NEW ROOFTOP UNIT. - BALANCE OF PIPING SYSTEM. EXISTING UNDER HOUSE NOT ON PRESSURE TEST. - GAS METER SERVICE - VALVE IN OFF POSITION. NOT TAGGED BY SOUTHWEST GAS - GAS LINE PRESS. TEST 12 PSI |
09/07/2006 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : The service is not per code.| 210* 1. I WILL NOT APPROVED THIS TYPE OF ANCHOR FOR THE SUPPORT OF THIS MAST OR STIFF ARM IT IS NOT EFFECTIVE 2. AC - IDENTIFY EQUIPMENT GROUNDS AND TERMINATE PROPERLY - NEED 36" IN FRONT OF DISCONNECT CLEAR NEED WORKING SERVICE RECEPTACLE ON ROOF REPAIR OR REPLACE EXISTING RECEPT. |
Completed Inspections
Permit Status: Expired
Permit Number: T06CM04478
Permit Description: INSTALL:A/C & HEATING:GAS LINE
R-1 Elec upgrade 100amps AND 2 CIRCUITS
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/12/2006 | MECHANICAL - FINAL | CWILLIAM | Approved |