Permit: T06CM04154
Permit Details
Apply Date:
07/14/2006
Applicant:
SISSY MCCABE
Description:
REPL: EXIST LIGHT POLE: WIRELESS ANTENNAS
Contractors:
- WESTOWER COMMUNICATIONS INC
Permit Reviews
Permit Number - T06CM04154
Permit Status: Final
Permit Description: REPL: EXIST LIGHT POLE: WIRELESS ANTENNAS
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 07/14/2006 | PLANS OK TO SUBMIT - COMM | 07/14/2006 | COMPLETED |
| 07/14/2006 | CELL TOWER/ANTENNAS | 08/17/2006 | COMPLETED |
| 09/08/2006 | RESUBMITTAL | 09/28/2006 | COMPLETED |
| 10/06/2006 | RESUBMITTAL | 10/10/2006 | COMPLETED |
| 10/10/2006 | RESUBMITTAL | 10/21/2006 | COMPLETED |
| 10/21/2006 | RESUBMITTAL | 11/28/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06CM04154
Permit Status: Final
Permit Description: REPL: EXIST LIGHT POLE: WIRELESS ANTENNAS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/14/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T06CM04154
Permit Description: REPL: EXIST LIGHT POLE: WIRELESS ANTENNAS
Total Completed Inspections - 10
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2006 | EXCAVATION/LAYOUT REBAR & ZON | AQUIROZ | Approved | IVRS - Inspection :* |
| 12/14/2006 | ELECTRIC - UFER | CCLEMENS | Approved | IVRS - Inspection :* 1. INSTALL ADDRESS ON SERVICE. 2. BOND WIRE FOR SERVICE RACEWAYS UNDERSIZED - NEC 250.102 C 3. TWO DIFFERENT SIZED CONDUCTORS (OR TYPE) NOT ALLOWED UNDER SAME TERMINATION - NEC 110.14 4. TIGHTEN ALL FITTINGS AND CONNECTIONS 5. PROTECT CONDUCTORS INTO POLE OK TO BACKFILL TRENCH |
| 12/14/2006 | OUTDOOR LIGHTING FINAL | CCLEMENS | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
| 12/14/2006 | ELECTRIC - OUTDOOR LIGHTING | CCLEMENS | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
| 12/14/2006 | ELECTRIC - UNDERGROUND | CCLEMENS | Approved | IVRS - Inspection :* |
| 12/20/2006 | ELECTRIC - INTERMEDIATE | CCLEMENS | Approved | IVRS - Inspection :* 1) CALL FOR FINAL WHEN ENERGIZED AND COMPLETE |
| 12/21/2006 | TEP CLEARANCE - AM | JWEATHER | Approved | ECO CLEARED PER C. CLEMENS |
| 01/10/2007 | ELECTRIC - FINAL | CCLEMENS | Approved | IVRS - Inspection :* |
| 01/11/2007 | BUILDING - FINAL | AQUIROZ | Approved | IVRS - Inspection :* |
| 01/16/2007 | PERMIT FINALED | BFLORES | Approved |