Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address:
125 W YAVAPAI RD
Address NEW:
125 W YAVAPAI RD
Apply Date:
07/14/2006
Applicant:
SISSY MCCABE
Description:
REPL: EXIST LIGHT POLE: WIRELESS ANTENNAS
Contractors:
  • WESTOWER COMMUNICATIONS INC

Permit Reviews

Permit Number - T06CM04154
Permit Status: Final
Permit Description: REPL: EXIST LIGHT POLE: WIRELESS ANTENNAS
Start Date Submittal Complete Date Status  
07/14/2006 PLANS OK TO SUBMIT - COMM 07/14/2006 COMPLETED Review Details
07/14/2006 CELL TOWER/ANTENNAS 08/17/2006 COMPLETED Review Details
09/08/2006 RESUBMITTAL 09/28/2006 COMPLETED Review Details
10/06/2006 RESUBMITTAL 10/10/2006 COMPLETED Review Details
10/10/2006 RESUBMITTAL 10/21/2006 COMPLETED Review Details
10/21/2006 RESUBMITTAL 11/28/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06CM04154
Permit Status: Final
Permit Description: REPL: EXIST LIGHT POLE: WIRELESS ANTENNAS
Total Outstanding Activity Conditions - 1
Date Name
07/14/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T06CM04154
Permit Description: REPL: EXIST LIGHT POLE: WIRELESS ANTENNAS
Total Completed Inspections - 10
Date Description Inspector Results Comments
11/20/2006 EXCAVATION/LAYOUT REBAR & ZON AQUIROZ Approved IVRS - Inspection :*
12/14/2006 ELECTRIC - UFER CCLEMENS Approved IVRS - Inspection :*
1. INSTALL ADDRESS ON SERVICE.
2. BOND WIRE FOR SERVICE RACEWAYS UNDERSIZED -
NEC 250.102 C
3. TWO DIFFERENT SIZED CONDUCTORS (OR TYPE) NOT ALLOWED UNDER SAME TERMINATION - NEC 110.14
4. TIGHTEN ALL FITTINGS AND CONNECTIONS
5. PROTECT CONDUCTORS INTO POLE

OK TO BACKFILL TRENCH
12/14/2006 OUTDOOR LIGHTING FINAL CCLEMENS Approved IVRS - Inspection :
See detailed listing on site.| 999*
12/14/2006 ELECTRIC - OUTDOOR LIGHTING CCLEMENS Approved IVRS - Inspection :
See detailed listing on site.| 999*
12/14/2006 ELECTRIC - UNDERGROUND CCLEMENS Approved IVRS - Inspection :*
12/20/2006 ELECTRIC - INTERMEDIATE CCLEMENS Approved IVRS - Inspection :*
1) CALL FOR FINAL WHEN ENERGIZED AND COMPLETE
12/21/2006 TEP CLEARANCE - AM JWEATHER Approved ECO CLEARED PER C. CLEMENS
01/10/2007 ELECTRIC - FINAL CCLEMENS Approved IVRS - Inspection :*
01/11/2007 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection :*
01/16/2007 PERMIT FINALED BFLORES Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW
4154-01-0001-01-0001.TIF CONSTRPLANS VIEW
4154-01-0001-01-0002.TIF CONSTRPLANS VIEW
4154-01-0001-01-0003.TIF CONSTRPLANS VIEW
4154-01-0001-01-0004.TIF CONSTRPLANS VIEW
4154-01-0001-01-0005.TIF CONSTRPLANS VIEW
4154-01-0001-01-0006.TIF CONSTRPLANS VIEW
4154-01-0001-01-0007.TIF CONSTRPLANS VIEW
4154-01-0001-01-0008.TIF CONSTRPLANS VIEW
4154-01-0001-01-0009.TIF CONSTRPLANS VIEW
4154-01-0001-01-0010.TIF CONSTRPLANS VIEW
4154-01-0001-01-0011.TIF CONSTRPLANS VIEW
4154-01-0001-01-0012.TIF CONSTRPLANS VIEW
4154-01-0001-01-0013.TIF CONSTRPLANS VIEW
4154-01-0001-01-0014.TIF CONSTRPLANS VIEW
4154-01-0001-01-0015.TIF CONSTRPLANS VIEW
4154-01-0001-01-0016.TIF CONSTRPLANS VIEW
4154-01-0001-01-0017.TIF CONSTRPLANS VIEW
4154-01-0001-01-0018.TIF CONSTRPLANS VIEW
None CONSTRPLANS VIEW