Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2006 | ELECTRIC - UFER | Approved | IVRS - Inspection :* 1. INSTALL ADDRESS ON SERVICE. 2. BOND WIRE FOR SERVICE RACEWAYS UNDERSIZED - NEC 250.102 C 3. TWO DIFFERENT SIZED CONDUCTORS (OR TYPE) NOT ALLOWED UNDER SAME TERMINATION - NEC 110.14 4. TIGHTEN ALL FITTINGS AND CONNECTIONS 5. PROTECT CONDUCTORS INTO POLE OK TO BACKFILL TRENCH |
|
| 12/13/2006 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* COULD NOT LOCATE NO MESSAGE |