Permit: T06CM04154

Parcel: 10603148A


Addresses:

125 W YAVAPAI RD


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T06CM04154

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
12/14/2006 ELECTRIC - UFER Approved IVRS - Inspection :*
1. INSTALL ADDRESS ON SERVICE.
2. BOND WIRE FOR SERVICE RACEWAYS UNDERSIZED -
NEC 250.102 C
3. TWO DIFFERENT SIZED CONDUCTORS (OR TYPE) NOT ALLOWED UNDER SAME TERMINATION - NEC 110.14
4. TIGHTEN ALL FITTINGS AND CONNECTIONS
5. PROTECT CONDUCTORS INTO POLE

OK TO BACKFILL TRENCH
12/13/2006 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*
COULD NOT LOCATE
NO MESSAGE