Permit Details

Status:
Expired
Type:
MULTI FAMILY ALTERATION
Apply Date:
05/31/2006
Applicant:
JACA DESIGN
Description:
GENERAL REPAIR & ELEC RECONNECT
Contractors:
  • KOBY GALLAGHER CONSTRUCTION INC

Permit Reviews

Permit Number - T06CM03260
Permit Status: Expired
Permit Description: GENERAL REPAIR & ELEC RECONNECT
Start Date Submittal Complete Date Status  
05/31/2006 OTHER 05/31/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06CM03260
Permit Status: Expired
Permit Description: GENERAL REPAIR & ELEC RECONNECT
Total Outstanding Activity Conditions - 1
Date Name
05/31/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T06CM03260
Permite Description: GENERAL REPAIR & ELEC RECONNECT
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
09/20/2006 ELECTRIC - INTERMEDIATE N/A Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
09/20/2006 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL ANTI-TIP DEVICE ON RANGE (SEE RANGE INSTRUCTIONS)
2. PROVIDE CONNECTOR FOR DISHWASHER CORD
3. PROVIDE CONNECTOR FOR HOOD WIRING
4. PROVIDE GFI PROTECTION FOR KITCHEN COUNTER RECEPTACLES.
5. GROUND ALL SWITCHES WITH EQUIPMENT GROUND AS REQUIRED.
6. PANEL DIRECTORY IS NOT CORRECTLY IDENTIFIED.
7. HALL SMOKE DETECTOR NOT INSTALLED PER MANUFACTURER INSTRUCTIONS.
8. PROVIDE DISCONNECTING MEANS FOR WATER HEATER.
9. BEDROOM LIGHT NOT WORKING
10. SEAL HOLE IN TOP OF SUB-PANEL

ALL WORK TO BE DONE BY LICENSED ELECTRICAL CONTRACTOR.
09/20/2006 PLUMBING - INTERMEDIATE N/A Not ready for Inspection IVRS - Inspection :*
09/20/2006 PLUMBING - FINAL N/A Not ready for Inspection IVRS - Inspection :*
- PLEASE HAVE PLAN AND PERMIT ON SITE AT TIME OF INSPECTION.
- UNABLE TO TELL SCOPE OF WORK.

Completed Inspections

Permit Status: Expired
Permit Number: T06CM03260
Permit Description: GENERAL REPAIR & ELEC RECONNECT
Total Completed Inspections - 2
Date Description Inspector Results Comments
09/20/2006 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection :*
09/20/2006 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*

Documents

File Name Document Type  
None DOCUMENTS VIEW
3260-01-0001-01-0001.TIF CONSTRPLANS VIEW
3260-01-0001-01-0002.TIF CONSTRPLANS VIEW
3260-01-0001-01-0003.TIF CONSTRPLANS VIEW
3260-01-0001-01-0004.TIF CONSTRPLANS VIEW