Permit Details

Status:
Final
Type:
MULTI FAMILY ALTERATION
Apply Date:
05/23/2006
Applicant:
JACA DESIGN
Description:
GENERAL REPAIRS, ELEC RECONNECT
Contractors:
  • POOR BOYS GENERAL REMODELING INC

Permit Reviews

Permit Number - T06CM03080
Permit Status: Final
Permit Description: GENERAL REPAIRS, ELEC RECONNECT
Start Date Submittal Complete Date Status  
05/23/2006 OTHER 05/23/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06CM03080
Permit Status: Final
Permit Description: GENERAL REPAIRS, ELEC RECONNECT
Total Outstanding Activity Conditions - 1
Date Name
05/23/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T06CM03080
Permit Description: GENERAL REPAIRS, ELEC RECONNECT
Total Completed Inspections - 8
Date Description Inspector Results Comments
08/31/2006 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
10/10/2006 ELECTRIC - INTERMEDIATE CCLEMENS Approved IVRS - Inspection :*
CHECK SMOKE DETECTOR PLACEMENT AND TIGHTEN GROUND SCREWS ON METAL BOXES.
12/18/2006 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*
PLUMBING FINAL OK
OK FOR C OF O S.T.O.I
12/20/2006 TEP CLEARANCE - AM BFLORES Approved RECN PER D.SANTA CRUZ
12/21/2006 ELECTRIC - RECONNECT RMAJUTA Approved IVRS - Inspection :
See detailed listing on site.| 999*
NO POWER YET
12/29/2006 ELECTRIC - FINAL CCLEMENS Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245$
1) PANEL DIRECTORY NOT PROPERLY INDENTIFIED-MAKE SURE IT IS CLEAR, LEGIABLE AND GOES TO WHAT IT SAYS-NEC 408.4
2) BEDROOM WIRING OUTLETS INCLUDING SMOKE DETECTORS NEED ARC FAULT PROTECTION-NEC 210.12
3) GROUND ALL SWITCHES-NEC 404.9 B
4) WATER HEATER MINIMUM SIZE GROUND TO BE #10 CU-NEC 250.122
5) PROVIDE DISCONNECTING MEANS FOR WATER HEATER NEC 422.31 B
6) INSTALL LIGHT BULBS (PROPERLY SIZED) IN ALL FIXTURES AND HOOD
7) PROVIDE CONNECTOR FOR DISHWASHER CORD-NEC 400.14
8) PROVIDE GFI PROTECTION FOR BATHROOM RECEPTACLE-NEC 210.8
9) SHEET METAL SCREWS NOT ALLOWED FOR PANEL GROUND BAR-NEC 250.8
10) SEPERATE NEUTRALS AND GROUNDS IN PANEL-NEC 250.24 A 5
11) MULTI WIRE BRANCH CKT PHASE CONDUCTORS TO TERMINATE ON SEPERATE PHASES IN PANEL-NEC 100
12) NEED LIGHT OR SWITCHED RECEPTACLE IN LIVING ROOM-NEC 210.70
13) AT ROOF TOP UNIT: IDENTIFY DISCONNECT, PROPERLY SECURE/MOUNT/SUPPORT DISCONNECT, INSTALL PROPER FUSES IN DISCONNECT AND EQUIPMENT GROUND TO UNIT UNDERSIZED
14) ALL WORK TO BE DONE BY LICENSED ELECTRICAL CONTRACTOR, WILL PAY FEE IF NOT CORRECT NEXT INSPECTION. HAVE CONTRACTOR CALL ME ASAP OR A STOP WORK ORDER MAY BE ISSUED
07/06/2007 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection :*
07/09/2007 PERMIT FINALED BFLORES Approved