Permit: T06CM03080

Parcel: 107092230


Addresses:

455 W KELSO ST #113


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM03080

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/03/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL RANGE
2. PANEL DIRECTORY STILL NOT CORRECT - SEE #1 FROM PREVIOUS INSPECTION.
3. WATER HEATER FUSES NOT INSTALLED IN DISCONNECT
4. CONNECT RANGE NEUTRAL TO NEUTRAL BAR -
NOT GROUND BAR.
5. PROVIDE LADDER FOR ROOF INSPECTION
6. THE THERMOSTAT DOES NOT TURN OFF AC?
06/19/2007 ELECTRIC - FINAL Cancelled IVRS - RI canceled
06/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES FROM PREV. INSP.
#6 - ABOVE LIGHT BULB IN HOOD
#8 - GFI PROTECTED CONDUIT IN BATHROOM REQUIRED
#14 - VERIFY LICENSED ELECTRICAL CONTRACTOR NAME AND PHONE NUMBER.

INSPECTOR WAS NOT NOTIFIED AS PER ITEM ABOVE
12/29/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245$
1) PANEL DIRECTORY NOT PROPERLY INDENTIFIED-MAKE SURE IT IS CLEAR, LEGIABLE AND GOES TO WHAT IT SAYS-NEC 408.4
2) BEDROOM WIRING OUTLETS INCLUDING SMOKE DETECTORS NEED ARC FAULT PROTECTION-NEC 210.12
3) GROUND ALL SWITCHES-NEC 404.9 B
4) WATER HEATER MINIMUM SIZE GROUND TO BE #10 CU-NEC 250.122
5) PROVIDE DISCONNECTING MEANS FOR WATER HEATER NEC 422.31 B
6) INSTALL LIGHT BULBS (PROPERLY SIZED) IN ALL FIXTURES AND HOOD
7) PROVIDE CONNECTOR FOR DISHWASHER CORD-NEC 400.14
8) PROVIDE GFI PROTECTION FOR BATHROOM RECEPTACLE-NEC 210.8
9) SHEET METAL SCREWS NOT ALLOWED FOR PANEL GROUND BAR-NEC 250.8
10) SEPERATE NEUTRALS AND GROUNDS IN PANEL-NEC 250.24 A 5
11) MULTI WIRE BRANCH CKT PHASE CONDUCTORS TO TERMINATE ON SEPERATE PHASES IN PANEL-NEC 100
12) NEED LIGHT OR SWITCHED RECEPTACLE IN LIVING ROOM-NEC 210.70
13) AT ROOF TOP UNIT: IDENTIFY DISCONNECT, PROPERLY SECURE/MOUNT/SUPPORT DISCONNECT, INSTALL PROPER FUSES IN DISCONNECT AND EQUIPMENT GROUND TO UNIT UNDERSIZED
14) ALL WORK TO BE DONE BY LICENSED ELECTRICAL CONTRACTOR, WILL PAY FEE IF NOT CORRECT NEXT INSPECTION. HAVE CONTRACTOR CALL ME ASAP OR A STOP WORK ORDER MAY BE ISSUED
12/19/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
12/19/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
POWER CK SYSTEM CALL FOR FINAL