Permit Details

Status:
Expired
Type:
COMMERCIAL ALTERATION
Address:
5266 S 12TH AV
Apply Date:
09/01/2006
Applicant:
SUN DEVIL FIRE EQUIPMENT INC ,
Description:
HOOD FIRE SYSTEM
Contractors:
  • SUN DEVIL FIRE EQUIPMENT INC ,

Permit Reviews

Permit Number - T06BU02210
Permit Status: Expired
Permit Description: HOOD FIRE SYSTEM
Start Date Submittal Complete Date Status  
09/01/2006 MECHANICAL 09/01/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06BU02210
Permit Status: Expired
Permit Description: HOOD FIRE SYSTEM
Total Outstanding Activity Conditions - 1
Date Name
09/01/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T06BU02210
Permite Description: HOOD FIRE SYSTEM
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
01/09/2007 FIRE - KITCHEN EXH HOOD FINAL N/A Denied 1.) Submit As-built.
2.) Fryer, larger dimension than on plan.
3.) Backshelves on range must show on plan.
4.) Old style filters.(mesh not allowed)
5.) Appliance line-up is different then on plan.
6.) 4.0 gallon cylinder provided , 6.0 gallon.
7.) No seperation between fryer an range burner.(16 inch seperation or 8 inch plate)
8.) Requires type I hood.
9.) Cylinder not located as on plan.
10.) Unable to test for activation and gas shut-off.
11.) Pull station not located as on plan.
12.) 15 flow points provided instead of 9 flow points.
13.) 450 D. temp. rating. detectors instead of 360.

Documents

File Name Document Type  
None DOCUMENTS VIEW
HOOD_001.TIF FIRE PLANS VIEW
HOOD_002.TIF FIRE PLANS VIEW