Permit: T06BU02210

Parcel: 137053110


Addresses:

5266 S 12TH AV


Inspection Status: Denied

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T06BU02210

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
01/09/2007 FIRE - KITCHEN EXH HOOD FINAL Denied 1.) Submit As-built.
2.) Fryer, larger dimension than on plan.
3.) Backshelves on range must show on plan.
4.) Old style filters.(mesh not allowed)
5.) Appliance line-up is different then on plan.
6.) 4.0 gallon cylinder provided , 6.0 gallon.
7.) No seperation between fryer an range burner.(16 inch seperation or 8 inch plate)
8.) Requires type I hood.
9.) Cylinder not located as on plan.
10.) Unable to test for activation and gas shut-off.
11.) Pull station not located as on plan.
12.) 15 flow points provided instead of 9 flow points.
13.) 450 D. temp. rating. detectors instead of 360.