Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T06BU02210
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/09/2007 | FIRE - KITCHEN EXH HOOD FINAL | Denied | 1.) Submit As-built. 2.) Fryer, larger dimension than on plan. 3.) Backshelves on range must show on plan. 4.) Old style filters.(mesh not allowed) 5.) Appliance line-up is different then on plan. 6.) 4.0 gallon cylinder provided , 6.0 gallon. 7.) No seperation between fryer an range burner.(16 inch seperation or 8 inch plate) 8.) Requires type I hood. 9.) Cylinder not located as on plan. 10.) Unable to test for activation and gas shut-off. 11.) Pull station not located as on plan. 12.) 15 flow points provided instead of 9 flow points. 13.) 450 D. temp. rating. detectors instead of 360. |