Permit Details

Status:
Closed
Type:
SINGLE FAMILY OTHER
Apply Date:
10/11/2005
Applicant:
VELAZAQUEZ RAFAEL
Description:
RECONNECT:GAS MH

Permit Reviews

Permit Number - T05PL01636
Permit Status: Closed
Permit Description: RECONNECT:GAS MH
Start Date Submittal Complete Date Status  
10/11/2005 PLUMBING 10/11/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05PL01636
Permit Status: Closed
Permit Description: RECONNECT:GAS MH
Total Outstanding Activity Conditions - 1
Date Name
10/11/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Closed
Permit Number: T05PL01636
Permite Description: RECONNECT:GAS MH
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
10/13/2005 PLUMBING - GAS PRESSURE TEST N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/13/2005 PLUMBING - GAS RECONNECT N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/13/2005 PLUMBING - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*PROVIDE AGA OR CSA APPROVED GAS SHUT OFF VALVE PRIOR TO FLEX WITH TEST ON ENTRIE GAS SYSTEM.
PROVIDE APPROVED COUPLINGTS ON GAS PIPING THREAD PROTECTORS ARE NOT APPROVED.
PROVIDE HANGERS AT 8' INTERVALS FOR PIPING NO PLUMBERS TAPE.
PLEASE CORRECT UNSANITARY CONDITION WITH YOUR PLUMBING WASTE SYSTEM. LEAKS AT SEVERAL LOCATIONS UNDER TRAILER, WASHER TIED IN TO WASTE MAIN, NO TRAP, DRAINAGE FITTING, VENT.
PROVIDE AGA OR CSA APPROVED GAS SHUT OFF VALVES AT APPLIANCES.
PROVIDE CORRECT FLUE VENT FOR WATER HEATER.
PROVIDE COMBUSTION AIR 100 SQ INCHES 12" FROM CEILING AND 12" FROM FLOOR WITH LOUVERS FOR WATER HEATER.