Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
11/18/2005
Applicant:
SANAGHAN EDWARD
Description:
install 5 gas/electric package air conditioners
Contractors:
  • ENERGY MANAGEMENT AND MAINTENANC

Outstanding Activity Conditions

Permit Number - T05ME00930
Permit Status: Final
Permit Description: install 5 gas/electric package air conditioners
Total Outstanding Activity Conditions - 1
Date Name
11/18/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T05ME00930
Permit Description: install 5 gas/electric package air conditioners
Total Completed Inspections - 3
Date Description Inspector Results Comments
12/28/2005 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
1) 3/8" I.D. X 18" GAS FLEX CONNECTORS NOT ADEQUATE FOR UNITS THAT EXCEED 111,720 BTU INPUT, A/C 1-1/2" I.D. FLEX, A/C 2-REQUIRES 3/4" GAS LINE AND 3/4" I.D. FLEX, A/C 3-REQUIRES 3/4" GAS LINE AND 3/4" I.D. FLEX, A/C 4-1/2" I.D. FLEX AND A/C 5-OK
01/05/2006 MECHANICAL - INTERMEDIATE JMILITEL Approved
01/06/2006 PERMIT FINALED JWEATHER Approved