Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
11/18/2005
Applicant:
SANAGHAN EDWARD
Description:
install 5 gas/electric package air conditioners
Contractors:
  • ENERGY MANAGEMENT AND MAINTENANC

Outstanding Activity Conditions

Permit Number - T05ME00930
Permit Status: Final
Permit Description: install 5 gas/electric package air conditioners
Total Outstanding Activity Conditions - 1
Date Name
11/18/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T05ME00930
Permit Description: install 5 gas/electric package air conditioners
Total Completed Inspections - 3
Date Description Inspector Results Comments
12/28/2005 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
1) 3/8" I.D. X 18" GAS FLEX CONNECTORS NOT ADEQUATE FOR UNITS THAT EXCEED 111,720 BTU INPUT, A/C 1-1/2" I.D. FLEX, A/C 2-REQUIRES 3/4" GAS LINE AND 3/4" I.D. FLEX, A/C 3-REQUIRES 3/4" GAS LINE AND 3/4" I.D. FLEX, A/C 4-1/2" I.D. FLEX AND A/C 5-OK
01/05/2006 MECHANICAL - INTERMEDIATE JMILITEL Approved
01/06/2006 PERMIT FINALED JWEATHER Approved