Permit: T05ME00930

Parcel: 12709007J

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/06/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
12/28/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) 3/8" I.D. X 18" GAS FLEX CONNECTORS NOT ADEQUATE FOR UNITS THAT EXCEED 111,720 BTU INPUT, A/C 1-1/2" I.D. FLEX, A/C 2-REQUIRES 3/4" GAS LINE AND 3/4" I.D. FLEX, A/C 3-REQUIRES 3/4" GAS LINE AND 3/4" I.D. FLEX, A/C 4-1/2" I.D. FLEX AND A/C 5-OK
12/13/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1) PLEASE PROVIDE ACCESS TO ROOF TOP