Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T05ME00733
Permit Details
Apply Date:
09/26/2005
Applicant:
MORANDO MINI
Description:
REPLACEMENT OF TRANE XL1600 5T GASPAC (KILLICK 628.1679)
Contractors:
- AMERICAN HOME MAINTENANCE INC *C
Outstanding Activity Conditions
Permit Number - T05ME00733
Permit Status: Expired
Permit Description: REPLACEMENT OF TRANE XL1600 5T
GASPAC (KILLICK 628.1679)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
09/26/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T05ME00733
Permite Description: REPLACEMENT OF TRANE XL1600 5T
GASPAC (KILLICK 628.1679)
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/13/2005 | MECHANICAL - FINAL | N/A | Partial Approval | IVRS - Inspection :* MINIMUM FUSE SIZE 45 AMPS CONDENSATE DRAIN PVC NEEDS TO BE PAINTED WHERE IS TRAP? BLOCK, CLAMP, 4 FT ON CENTERS. CONDENSATE TERMINATING ONTO BRICK SIDEWALK. GAS PRESS. TEST 20 PSI OK |