Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
220 W LINCOLN ST #02
Apply Date:
12/19/2005
Applicant:
WILKOWSKI ELECTRIC *C
Description:
ELEC UPGRADE 100AMPS (APA) REV1:REWIRE UNIT#2 &ADD SMOKE DETECTORS TO UNIT #1 EXTENDED PERMIT FOR ELECTRIC RECONNECT #2 AND #3
Contractors:
  • WILKOWSKI ELECTRIC *C

Permit Reviews

Permit Number - T05EL02501
Permit Status: Expired
Permit Description: ELEC UPGRADE 100AMPS (APA) REV1:REWIRE UNIT#2 &ADD SMOKE DETECTORS TO UNIT #1 EXTENDED PERMIT FOR ELECTRIC RECONNECT #2 AND #3
Start Date Submittal Complete Date Status  
05/25/2006 OTHER 05/25/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05EL02501
Permit Status: Expired
Permit Description: ELEC UPGRADE 100AMPS (APA) REV1:REWIRE UNIT#2 &ADD SMOKE DETECTORS TO UNIT #1 EXTENDED PERMIT FOR ELECTRIC RECONNECT #2 AND #3
Total Outstanding Activity Conditions - 1
Date Name
12/19/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T05EL02501
Permite Description: ELEC UPGRADE 100AMPS (APA) REV1:REWIRE UNIT#2 &ADD SMOKE DETECTORS TO UNIT #1 EXTENDED PERMIT FOR ELECTRIC RECONNECT #2 AND #3
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
06/09/2006 ELECTRIC - UNDERGROUND N/A Partial Approval IVRS - Inspection :*
11/08/2006 ELECTRIC - INTERMEDIATE N/A Partial Approval IVRS - Inspection :*
12/30/2005 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. USE SPLIT BOLT OUTSIDE OF SERVICE PANEL TO TAP GROUNDING ELECTRODE CONDUCTOR TO SECOND SERVICE.
2. GAS & WATER TO BOTH UNITS TO BE BONDED.
3. VERIFY PERMITS & PLANS FOR INSIDE NEW WIRING, IF NOT PLEASE OBTAIN, NO POWER CLEARANCE FOR SERVICES UNTIL NEW WIRING FOR BOTH UNITS HAS BEEN PERMITTED & INSPECTED. THIS ALSO APPLIES TO WASHROOM BLD.
4. USE SCH 80 PVC WHERE EXPOSED BELOW SERVICES
5. DERATE BRANCH CIRCUITS IN 1 1/2" CONDUITS TO UNIT #2 PER NEC

Completed Inspections

Permit Status: Expired
Permit Number: T05EL02501
Permit Description: ELEC UPGRADE 100AMPS (APA) REV1:REWIRE UNIT#2 &ADD SMOKE DETECTORS TO UNIT #1 EXTENDED PERMIT FOR ELECTRIC RECONNECT #2 AND #3
Total Completed Inspections - 1
Date Description Inspector Results Comments
06/21/2006 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED FOR #2 & #3 PER D. SANTACRUZ

Documents

File Name Document Type  
None DOCUMENTS VIEW