Permit: T05EL02501

Parcel: 120070780

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL02501

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
08/17/2015 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/17/2015 ELECTRIC - FINAL Denied **UNIT #3**
1. COMPLY WITH PREVIOUS NOTES #1 AND #3
2. SMOKE ALARMS MISSING PER CODE
**UNIT #2**
PROVIDE PLANS AND INSPECTION CARD. **NOTE: WINDOWS IN BEDROOMS DO NOT MEET EGRESS REQUIREMENTS**
11/08/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) ARC FAULTS REQUIRED BOTH UNITS, BEDROOMS OR SLEEPING AREA
2) NO DRYWALL YET #2
3) RANGE HOOD NOT INSTALLED #1, COVERS MISSING
06/20/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
06/09/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUNDING ELECTRODE SYSTEM REQUIRED AT BLD #2 PER NEC ART 250
2. ROMEX NOT RATED FOR UNDERGROUND USE.
3. KITCHEN COUNTERS REQUIRE MIN. 2 CKTS PER NEC.
SEE PLAN
01/13/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*PLANS MUST BE STAMPED BY PLAN CHECK COT-ALSO MUST BE PERMITED.
WASHROOM NOT SHOWN
A RE INSPECTION FEE WILL BE ASSESED NEXT INSPECTION IF NO COMPLIANCE
01/10/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
VERIFY #3 NOTE LAST INSP.
12/30/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. USE SPLIT BOLT OUTSIDE OF SERVICE PANEL TO TAP GROUNDING ELECTRODE CONDUCTOR TO SECOND SERVICE.
2. GAS & WATER TO BOTH UNITS TO BE BONDED.
3. VERIFY PERMITS & PLANS FOR INSIDE NEW WIRING, IF NOT PLEASE OBTAIN, NO POWER CLEARANCE FOR SERVICES UNTIL NEW WIRING FOR BOTH UNITS HAS BEEN PERMITTED & INSPECTED. THIS ALSO APPLIES TO WASHROOM BLD.
4. USE SCH 80 PVC WHERE EXPOSED BELOW SERVICES
5. DERATE BRANCH CIRCUITS IN 1 1/2" CONDUITS TO UNIT #2 PER NEC