Permit: T05EL02457
Permit Details
Apply Date:
12/13/2005
Applicant:
CORNETA BERNARDITA
Description:
RECONNECT:ELECTRIC BUSINESS
Outstanding Activity Conditions
Permit Number - T05EL02457
Permit Status: Closed
Permit Description: RECONNECT:ELECTRIC BUSINESS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/13/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Closed
Permit Number: T05EL02457
Permit Description: RECONNECT:ELECTRIC BUSINESS
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2005 | ELECTRIC - RECONNECT | RHOLLAND | Approved | IVRS - Inspection : See detailed listing on site.| 999*ADDRESS TO BE POSTED ON BUILDING OUTDOOR LIGHTS TO BE CORRECTLY WIRED FOR WEATHER PROOF LOCATION LIGHTS & WIRING METHOD NM CABLE NOT FOR USE AT FRONT COUNTER TIGHTEN LOOSE FITTINGS WE HAVE GROUNDED RECEPTACLES ON AN UNGROUNDED SYSTEM ALSO WE HAVE EXCESSIVE PAINT ON RECEPTACLES PROPERLY SUPPORT CONDUITS LABLE SERVICE DISCONNECTS SERVICE DISCONNECTS AND CONDUCTORS IN DETERIORATED CONDITION A SERVICE UPGRADE IS NEEDED A/C IS NOT WIRED TO CODE (3) PLEASE HAVE A LICENSED 2-11 ELECTRICAL CONTRACTOR PERFORM WORK |
| 12/22/2005 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
| 01/20/2006 | TEP CLEARANCE - AM | JKOZUCH | Approved | RECN |