Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2006 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 12/22/2005 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999*ADDRESS TO BE POSTED ON BUILDING OUTDOOR LIGHTS TO BE CORRECTLY WIRED FOR WEATHER PROOF LOCATION LIGHTS & WIRING METHOD NM CABLE NOT FOR USE AT FRONT COUNTER TIGHTEN LOOSE FITTINGS WE HAVE GROUNDED RECEPTACLES ON AN UNGROUNDED SYSTEM ALSO WE HAVE EXCESSIVE PAINT ON RECEPTACLES PROPERLY SUPPORT CONDUITS LABLE SERVICE DISCONNECTS SERVICE DISCONNECTS AND CONDUCTORS IN DETERIORATED CONDITION A SERVICE UPGRADE IS NEEDED A/C IS NOT WIRED TO CODE (3) PLEASE HAVE A LICENSED 2-11 ELECTRICAL CONTRACTOR PERFORM WORK |