Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
MULTI FAMILY OTHER
Apply Date:
12/12/2005
Applicant:
B A ELECTRIC *T
Description:
REPAIR:LIFELINE AND ADD CIRCUIT (APA)
Contractors:
  • B A ELECTRIC *T

Outstanding Activity Conditions

Permit Number - T05EL02452
Permit Status: Final
Permit Description: REPAIR:LIFELINE AND ADD CIRCUIT (APA)
Total Outstanding Activity Conditions - 1
Date Name
12/12/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T05EL02452
Permit Description: REPAIR:LIFELINE AND ADD CIRCUIT (APA)
Total Completed Inspections - 4
Date Description Inspector Results Comments
12/14/2005 ELECTRIC - FINAL CCLEMENS Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*NEED TO GROUND ENCLOSURE WHERE SPLICE WAS MADE IN CORD NEC 250.86
SECURE LIQUID TIGHT FLEX WITHIN 12" OF ENCLOSURE ENTRANCE NEC. 350.30 (A)
PROVIDE CONNECTOR WHERE FLEX ENTERS ENCLOSURE AND PROVIDE PROTECTION AGAINST ABRASION AT OTHER END NEC 312.5
01/09/2006 ELECTRIC - INTERMEDIATE CCLEMENS Approved
01/09/2006 ELECTRIC - UNDERGROUND CCLEMENS Approved
01/10/2006 PERMIT FINALED JKOZUCH Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW