Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/14/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*NEED TO GROUND ENCLOSURE WHERE SPLICE WAS MADE IN CORD NEC 250.86 SECURE LIQUID TIGHT FLEX WITHIN 12" OF ENCLOSURE ENTRANCE NEC. 350.30 (A) PROVIDE CONNECTOR WHERE FLEX ENTERS ENCLOSURE AND PROVIDE PROTECTION AGAINST ABRASION AT OTHER END NEC 312.5 |