Permit: T05EL02252
Permit Details
Apply Date:
11/08/2005
Applicant:
D S ELECTRIC *C
Description:
UPGRD 100 AMP TO 200 AMP ( APA )
Contractors:
- D S ELECTRIC *C
Outstanding Activity Conditions
Permit Number - T05EL02252
Permit Status: Expired
Permit Description: UPGRD 100 AMP TO 200 AMP ( APA )
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/08/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T05EL02252
Permite Description: UPGRD 100 AMP TO 200 AMP ( APA )
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/16/2005 | ELECTRIC - UNDERGROUND | N/A | Partial Approval | IVRS - Inspection :* |
| 11/16/2005 | ELECTRIC - INTERMEDIATE | N/A | Partial Approval | IVRS - Inspection :* |
| 11/16/2005 | ELECTRIC - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1) RECEPTACLE COVER TO BE WEATHER PROOF WHETHER OR NOT PLUGGED INTO 406.8 2) PLEASE VERIFY GROUNDING CONDUCTOR TO A/C AS 250.122 3) PLEASE VERIFY PERMIT FOR NEW A/C 4) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE 110.26 (CUT DOWN PIPE FLUSH WITH GRADE) 5) TIGHTEN FITTINGS AT POOL PANEL |