Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/16/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) RECEPTACLE COVER TO BE WEATHER PROOF WHETHER OR NOT PLUGGED INTO 406.8 2) PLEASE VERIFY GROUNDING CONDUCTOR TO A/C AS 250.122 3) PLEASE VERIFY PERMIT FOR NEW A/C 4) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE 110.26 (CUT DOWN PIPE FLUSH WITH GRADE) 5) TIGHTEN FITTINGS AT POOL PANEL |