Permit Details

Status:
Withdrwn
Type:
SINGLE FAMILY OTHER
Address NEW:
6841 E FLAMENCO DR
Apply Date:
11/01/2005
Applicant:
CASTRO LUIS LOPEZ
Description:
UPGRADE:ELECTRIC 200AMP:RELOCATE

Permit Reviews

Permit Number - T05EL02215
Permit Status: Withdrwn
Permit Description: UPGRADE:ELECTRIC 200AMP:RELOCATE
Start Date Submittal Complete Date Status  
11/01/2005 ELECTRICAL 11/01/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05EL02215
Permit Status: Withdrwn
Permit Description: UPGRADE:ELECTRIC 200AMP:RELOCATE
Total Outstanding Activity Conditions - 1
Date Name
11/01/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Withdrwn
Permit Number: T05EL02215
Permite Description: UPGRADE:ELECTRIC 200AMP:RELOCATE
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
ELECTRIC - SERVICE UPGRADE N/A Not Inspected
05/05/2006 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO FURTHER INSPECTIONS UNTIL A LICENSED CONTRACTOR CONTACTS US.
MY NUMBER IS 909-4749/OFFICE 791-5550 EX 1136
11/04/2005 ELECTRIC - INTERMEDIATE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*PLEASE VERIFY 2ND GROUND ROD, WATER AND GS BONDS
USE APPROVED FITTINGS FOR FLEX CONDUIT AND PROVIDE A DRIP LOOP OR USE WEATHER PROOF RACEWAY
BREAKER TO BE LISTED FOR USE BY MANUFACTURER
PLEASE VERIFY DE RATING AS PER 310.15
ENTRANCES ABOVE CURRENT CARRING PARTS TO USE AN APPROVED SEALING DEVICE
MAINTAIN CLEARANCES AS PER 680.10 FOR SERVICE CONDUCTORS
CORRECTLY IDENTIFY GROUNDED CONDUCTOR
A PERMANENT METAL ADDRESS LABEL IS NEEDED
WE HAVE MULTIPLE TERMINATIONS AT LUG
PLEASE VERIFY PERMIT FOR NEW AC UNIT
CUSTOMER STATES THEY ARE NOT DOING WORK. PLEASE VERIFY LICENSED ELECTRICAL CONTRACTOR
11/04/2005 ELECTRIC - SERVICE RELOCATION N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*

Completed Inspections

Permit Status: Withdrwn
Permit Number: T05EL02215
Permit Description: UPGRADE:ELECTRIC 200AMP:RELOCATE
Total Completed Inspections - 1
Date Description Inspector Results Comments
01/18/2006 ELECTRIC - UNDERGROUND RSUBA Approved IVRS - Inspection :*

Documents

File Name Document Type  
None DOCUMENTS VIEW