Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05EL02215
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/18/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/04/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*PLEASE VERIFY 2ND GROUND ROD, WATER AND GS BONDS USE APPROVED FITTINGS FOR FLEX CONDUIT AND PROVIDE A DRIP LOOP OR USE WEATHER PROOF RACEWAY BREAKER TO BE LISTED FOR USE BY MANUFACTURER PLEASE VERIFY DE RATING AS PER 310.15 ENTRANCES ABOVE CURRENT CARRING PARTS TO USE AN APPROVED SEALING DEVICE MAINTAIN CLEARANCES AS PER 680.10 FOR SERVICE CONDUCTORS CORRECTLY IDENTIFY GROUNDED CONDUCTOR A PERMANENT METAL ADDRESS LABEL IS NEEDED WE HAVE MULTIPLE TERMINATIONS AT LUG PLEASE VERIFY PERMIT FOR NEW AC UNIT CUSTOMER STATES THEY ARE NOT DOING WORK. PLEASE VERIFY LICENSED ELECTRICAL CONTRACTOR |