Permit: T05EL02215

Parcel: 133222520


Addresses:

6841 E FLAMENCO DR


Inspection Status: Denied

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05EL02215

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Denied

Date Description Inspector Results Comments
05/05/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/18/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/04/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*PLEASE VERIFY 2ND GROUND ROD, WATER AND GS BONDS
USE APPROVED FITTINGS FOR FLEX CONDUIT AND PROVIDE A DRIP LOOP OR USE WEATHER PROOF RACEWAY
BREAKER TO BE LISTED FOR USE BY MANUFACTURER
PLEASE VERIFY DE RATING AS PER 310.15
ENTRANCES ABOVE CURRENT CARRING PARTS TO USE AN APPROVED SEALING DEVICE
MAINTAIN CLEARANCES AS PER 680.10 FOR SERVICE CONDUCTORS
CORRECTLY IDENTIFY GROUNDED CONDUCTOR
A PERMANENT METAL ADDRESS LABEL IS NEEDED
WE HAVE MULTIPLE TERMINATIONS AT LUG
PLEASE VERIFY PERMIT FOR NEW AC UNIT
CUSTOMER STATES THEY ARE NOT DOING WORK. PLEASE VERIFY LICENSED ELECTRICAL CONTRACTOR