Permit: T05EL02163
Permit Details
Apply Date:
10/21/2005
Applicant:
PRESIDIO ELECTRIC SERVICES INC,*C
Description:
REPLACE 200 AMP
Contractors:
- PRESIDIO ELECTRIC SERVICES INC,*C
Outstanding Activity Conditions
Permit Number - T05EL02163
Permit Status: Final
Permit Description: REPLACE 200 AMP
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
10/21/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T05EL02163
Permit Description: REPLACE 200 AMP
Total Completed Inspections - 2
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/14/2005 | ELECTRIC - FINAL | CCLEMENS | Approved | IVRS - Inspection : The service is not per code.| 210$ 1. PROPERLY STRAP CONDUITS ENTERING PANEL - NEC 344.30(A) AND NEC 358.30(A) 2. WHERE THOSE CONDUITS ARE USED AS AN EQUIPMENT - GROUND, MAKE SURE THEY ARE MADE UP TIGHT AND PROVIDE A PROPER GROUND PATH NEC 250.4(A)5 3. BOND WATER AND GAS PIPES TO SERVICE - NEC 250.104(A) AND (B) 4. INSTALL SEALING TYPE LOCKNUTS WHERE A.C. L.B. ENTERS PANEL ON SIDE OF ENCLOSURE NEC 110.11 5. MARK SERVICE DISCONNECT ON PANEL NEC 110.22 |
07/24/2006 | PERMIT FINALED | LJACKSON | Approved |