Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/20/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/14/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210$ 1. PROPERLY STRAP CONDUITS ENTERING PANEL - NEC 344.30(A) AND NEC 358.30(A) 2. WHERE THOSE CONDUITS ARE USED AS AN EQUIPMENT - GROUND, MAKE SURE THEY ARE MADE UP TIGHT AND PROVIDE A PROPER GROUND PATH NEC 250.4(A)5 3. BOND WATER AND GAS PIPES TO SERVICE - NEC 250.104(A) AND (B) 4. INSTALL SEALING TYPE LOCKNUTS WHERE A.C. L.B. ENTERS PANEL ON SIDE OF ENCLOSURE NEC 110.11 5. MARK SERVICE DISCONNECT ON PANEL NEC 110.22 |
|
| 11/23/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*12:30 PM NO ANSWER PLEASE CALL TO RE SCHEDULE |