Permit: T05EL02163

Parcel: 12515052A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL02163

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/20/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/14/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210$
1. PROPERLY STRAP CONDUITS ENTERING PANEL - NEC 344.30(A) AND NEC 358.30(A)
2. WHERE THOSE CONDUITS ARE USED AS AN EQUIPMENT - GROUND, MAKE SURE THEY ARE MADE UP TIGHT AND PROVIDE A PROPER GROUND PATH NEC 250.4(A)5
3. BOND WATER AND GAS PIPES TO SERVICE - NEC 250.104(A) AND (B)
4. INSTALL SEALING TYPE LOCKNUTS WHERE A.C. L.B. ENTERS PANEL ON SIDE OF ENCLOSURE NEC 110.11
5. MARK SERVICE DISCONNECT ON PANEL NEC 110.22
11/23/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*12:30 PM NO ANSWER PLEASE CALL TO RE SCHEDULE