Description:
UPGRADE 3 PHASE ELECTRIC 600AMPS
Contractors:
  • HARDIN REFRIGERATION INC ,

Permit Reviews

Permit Number - T05EL02045
Permit Status: Expired
Permit Description: UPGRADE 3 PHASE ELECTRIC 600AMPS
Start Date Submittal Complete Date Status  
10/04/2005 ELECTRICAL 10/05/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05EL02045
Permit Status: Expired
Permit Description: UPGRADE 3 PHASE ELECTRIC 600AMPS
Total Outstanding Activity Conditions - 1
Date Name
10/04/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T05EL02045
Permite Description: UPGRADE 3 PHASE ELECTRIC 600AMPS
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
PERMIT FINALED N/A Not Inspected
10/08/2007 ELECTRIC - FINAL N/A Partial Approval IVRS - Inspection :*
1) CALL FOR FINAL AFTER TIE IN

Completed Inspections

Permit Status: Expired
Permit Number: T05EL02045
Permit Description: UPGRADE 3 PHASE ELECTRIC 600AMPS
Total Completed Inspections - 3
Date Description Inspector Results Comments
03/31/2006 ELECTRIC - UNDERGROUND DSANTACR Approved IVRS - Inspection :*
- OK U.G. ALSO NOTE THAT 3" INSTALLED IN SAME TRENCH AS 4" - 3" IS FOR FUTURE.
- BOND BUSHINGS REQUIRED AHEAD OF OVERCURRENT PROTECTION AT SERVICE, OK THREADED HUBS.
10/25/2006 ELECTRIC - SERVICE UPGRADE DSANTACR Approved IVRS - Inspection :
See detailed listing on site.| 999*
1. BOND BUSHINGS REQUIRED IN CT RISER CONDUITS, BOND PER 250.66 FOR WIRE SIZE AHEAD OF OVERCURRENT PROTECTION.
2. BOND NEUTRALS IN DISCONNECTS AT SERVICE
3. BOND WATER & GAS
4. BONDING AT SECOND BLD. PER 250.66 & 250-120 WHERE APPLICABLE. ALSO, PLAN CALLS FOR #2 CU, GRND, WITH FEEDERS TO 2ND BLD.
5. INSTALL BUSHING #4 AWG & LARGER PER NEC
6. SUPPORT CONDUITS WITHIN 3' OF TERM.
7. LABEL DISCONNECTS & SERVICE.
10/09/2007 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED PER D. SANTACRUZ