Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T05EL02045
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/31/2007 | ELECTRIC - SERVICE UPGRADE | Approved | ||
01/22/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1. GROUNDING AT SERVICE, UNPROTECTED CONDUCTORS PER 250.66 -- GROUND WIRE USED IS TOO SMALL. 2. PER 3005-I GROUND (EQUIP) MUST BE IN SAME CONDUIT AS FEEDERS. 3. NEUTRALS MUST BE IN SAME RACEWAY AS FEEDERS. 4. EQUIP. GROUND TO BE RUN IN EACH CONDUIT WHEN USE OF PARALLEL FEEDS. PER 250.122 F -- SEE PLANS 5. BOND WATER PIPING BOTH BLDS. |
|
10/25/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND BUSHINGS REQUIRED IN CT RISER CONDUITS, BOND PER 250.66 FOR WIRE SIZE AHEAD OF OVERCURRENT PROTECTION. 2. BOND NEUTRALS IN DISCONNECTS AT SERVICE 3. BOND WATER & GAS 4. BONDING AT SECOND BLD. PER 250.66 & 250-120 WHERE APPLICABLE. ALSO, PLAN CALLS FOR #2 CU, GRND, WITH FEEDERS TO 2ND BLD. 5. INSTALL BUSHING #4 AWG & LARGER PER NEC 6. SUPPORT CONDUITS WITHIN 3' OF TERM. 7. LABEL DISCONNECTS & SERVICE. |