Permit: T05EL02045

Parcel: 124161720


Addresses:

950 S PARK AV


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T05EL02045

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
03/31/2007 ELECTRIC - SERVICE UPGRADE Approved
01/22/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES:
1. GROUNDING AT SERVICE, UNPROTECTED CONDUCTORS
PER 250.66 -- GROUND WIRE USED IS TOO SMALL.
2. PER 3005-I GROUND (EQUIP) MUST BE IN SAME CONDUIT AS FEEDERS.
3. NEUTRALS MUST BE IN SAME RACEWAY AS FEEDERS.
4. EQUIP. GROUND TO BE RUN IN EACH CONDUIT WHEN USE OF PARALLEL FEEDS. PER 250.122 F -- SEE PLANS
5. BOND WATER PIPING BOTH BLDS.
10/25/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOND BUSHINGS REQUIRED IN CT RISER CONDUITS, BOND PER 250.66 FOR WIRE SIZE AHEAD OF OVERCURRENT PROTECTION.
2. BOND NEUTRALS IN DISCONNECTS AT SERVICE
3. BOND WATER & GAS
4. BONDING AT SECOND BLD. PER 250.66 & 250-120 WHERE APPLICABLE. ALSO, PLAN CALLS FOR #2 CU, GRND, WITH FEEDERS TO 2ND BLD.
5. INSTALL BUSHING #4 AWG & LARGER PER NEC
6. SUPPORT CONDUITS WITHIN 3' OF TERM.
7. LABEL DISCONNECTS & SERVICE.