Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
901 S FREMONT AV
Address NEW:
901 S FREMONT AV
Apply Date:
09/16/2005
Applicant:
SERGIO HURTADO
Description:
INSTALL NEW ELECTRIC BOX & REWIRING

Outstanding Activity Conditions

Permit Number - T05EL01910
Permit Status: Final
Permit Description: INSTALL NEW ELECTRIC BOX & REWIRING
Total Outstanding Activity Conditions - 1
Date Name
09/16/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T05EL01910
Permit Description: INSTALL NEW ELECTRIC BOX & REWIRING
Total Completed Inspections - 6
Date Description Inspector Results Comments
11/23/2005 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection :
See detailed listing on site.| 999*GROUND WIRE AT FIRST GROUND ROD TO SECOND ROD NOT TERMINATED PROPERLY IN CLAMP, ALSO AT 2ND ROD TO WATER PIPE.
GROUND WATER & GAS PIPING CLOSET TO HOUSE. PREFERED AT ENTRY TO DWELLING
INSTALL BUSHING BEHING PANEL WHERE CONDUCTORS EXIT.
WHERE DID YOU SPLICE NEW WIRING TO OLD. NO CABLE SHEATH INSIDE PANEL, MUST HAVE 1/4" MIN.
VERIFY PERMITS & INSPECTION APPROVALS FOR NEW WIRING INSIDE HOUSE.
USE CLAMP FOR GROUND WIRE AT BOTTOM OF SERVICE PANEL
HOUSE UNOCCUPIED-VERIFY PH # NAME OF C-11 LICENSED CONT.
03/02/2006 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection :*
03/02/2006 ELECTRIC - CABLE DROP DSANTACR Approved IVRS - Inspection :*
03/02/2006 ELECTRIC - UNDERGROUND DSANTACR Approved IVRS - Inspection :*
03/03/2006 PERMIT FINALED JKOZUCH Approved
03/03/2006 TEP CLEARANCE - AM JKOZUCH Approved INCR

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CONSTRPLANS VIEW