Permit: T05EL01910
Permit Details
Apply Date:
09/16/2005
Applicant:
SERGIO HURTADO
Description:
INSTALL NEW ELECTRIC BOX & REWIRING
Outstanding Activity Conditions
Permit Number - T05EL01910
Permit Status: Final
Permit Description: INSTALL NEW ELECTRIC BOX & REWIRING
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/16/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T05EL01910
Permit Description: INSTALL NEW ELECTRIC BOX & REWIRING
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/23/2005 | ELECTRIC - INTERMEDIATE | DSANTACR | Approved | IVRS - Inspection : See detailed listing on site.| 999*GROUND WIRE AT FIRST GROUND ROD TO SECOND ROD NOT TERMINATED PROPERLY IN CLAMP, ALSO AT 2ND ROD TO WATER PIPE. GROUND WATER & GAS PIPING CLOSET TO HOUSE. PREFERED AT ENTRY TO DWELLING INSTALL BUSHING BEHING PANEL WHERE CONDUCTORS EXIT. WHERE DID YOU SPLICE NEW WIRING TO OLD. NO CABLE SHEATH INSIDE PANEL, MUST HAVE 1/4" MIN. VERIFY PERMITS & INSPECTION APPROVALS FOR NEW WIRING INSIDE HOUSE. USE CLAMP FOR GROUND WIRE AT BOTTOM OF SERVICE PANEL HOUSE UNOCCUPIED-VERIFY PH # NAME OF C-11 LICENSED CONT. |
| 03/02/2006 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection :* |
| 03/02/2006 | ELECTRIC - CABLE DROP | DSANTACR | Approved | IVRS - Inspection :* |
| 03/02/2006 | ELECTRIC - UNDERGROUND | DSANTACR | Approved | IVRS - Inspection :* |
| 03/03/2006 | PERMIT FINALED | JKOZUCH | Approved | |
| 03/03/2006 | TEP CLEARANCE - AM | JKOZUCH | Approved | INCR |