Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/03/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/23/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*GROUND WIRE AT FIRST GROUND ROD TO SECOND ROD NOT TERMINATED PROPERLY IN CLAMP, ALSO AT 2ND ROD TO WATER PIPE. GROUND WATER & GAS PIPING CLOSET TO HOUSE. PREFERED AT ENTRY TO DWELLING INSTALL BUSHING BEHING PANEL WHERE CONDUCTORS EXIT. WHERE DID YOU SPLICE NEW WIRING TO OLD. NO CABLE SHEATH INSIDE PANEL, MUST HAVE 1/4" MIN. VERIFY PERMITS & INSPECTION APPROVALS FOR NEW WIRING INSIDE HOUSE. USE CLAMP FOR GROUND WIRE AT BOTTOM OF SERVICE PANEL HOUSE UNOCCUPIED-VERIFY PH # NAME OF C-11 LICENSED CONT. |