Permit: T05EL01866
Permit Details
Apply Date:
09/12/2005
Applicant:
DAY BREAK ELECTRIC INC , *C
Description:
ELEC UPGRADE FROM 100 AMP TO 200 AMP (APA)
Contractors:
- DAY BREAK ELECTRIC INC , *C
Outstanding Activity Conditions
Permit Number - T05EL01866
Permit Status: Expired
Permit Description: ELEC UPGRADE FROM 100 AMP TO 200 AMP (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/12/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T05EL01866
Permite Description: ELEC UPGRADE FROM 100 AMP TO 200 AMP (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/13/2005 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) INSTALL BUSHED CONNECTOR AT CONDUIT END WHERE CABLE EXITS AT TOP OF PANEL TO PROTECT FROM ABRASION 2) 3/4" CONDUIT FOR A/C NOT SUPPORTED BELOW ROOF OVERHANG, ALSO 3/4" CONNECT OR AT LB TERMINATION INTO PANEL NOT APPROVED WIRING METHOD, USE PROPER FITTING AND LOCK NUTS 3) VERIFY PERMIT FOR NEW A/C UNIT INSTALL |