Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/13/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) INSTALL BUSHED CONNECTOR AT CONDUIT END WHERE CABLE EXITS AT TOP OF PANEL TO PROTECT FROM ABRASION 2) 3/4" CONDUIT FOR A/C NOT SUPPORTED BELOW ROOF OVERHANG, ALSO 3/4" CONNECT OR AT LB TERMINATION INTO PANEL NOT APPROVED WIRING METHOD, USE PROPER FITTING AND LOCK NUTS 3) VERIFY PERMIT FOR NEW A/C UNIT INSTALL |