Permit: T05EL01658
Permit Details
Apply Date:
08/10/2005
Applicant:
MEHL ELECTRIC SERVICE INC,*C
Description:
REPAIR:SERVICE ELECTRIC (APA)
Contractors:
- MEHL ELECTRIC SERVICE INC,*C
Outstanding Activity Conditions
Permit Number - T05EL01658
Permit Status: Final
Permit Description: REPAIR:SERVICE ELECTRIC (APA)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
08/10/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T05EL01658
Permit Description: REPAIR:SERVICE ELECTRIC (APA)
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/15/2005 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) LINE LOAD CONDUCTORS IN SAME RACEWAY OR GUTTER, UNPROTECTED UTILITY AND CUSTOMER 230.7 NEC 2) LOAD CONDUCTORS TO MODULAR OFFICE NOT PROTECTED PROPERLY 3) CT AND METER SEALED WITH TEP SEALS 4) VERIFY SYSTEM IS GROUNDED PER 250 NEC COULD NOT VERIFY EARTH GROUND OR BLDG STEEL 5) CONTRACTOR NOT ON SITE, OPEN CT AND GUTTER VERIFY NEUTRAL BONDED, BOND BUSHINGS OR BOND LOCK NUTS INSTALLED 6) NEUTRAL CONDUCTOR NOT RUN TO MAIN DISCONNECT PER 250 NEC |