Permit: T05EL01657
Permit Details
Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
3735 E MONTE VISTA DR
Address NEW:
3735 E MONTE VISTA DR
Apply Date:
08/10/2005
Applicant:
ALANSARY ABDULLAH D
Description:
UPGRADE:ELECTRIC TO 200AMPS
Permit Reviews
Permit Number - T05EL01657
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC TO 200AMPS
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/10/2005 | ELECTRICAL | 08/10/2005 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05EL01657
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC TO 200AMPS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/10/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T05EL01657
Permit Description: UPGRADE:ELECTRIC TO 200AMPS
Total Completed Inspections - 7
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/21/2005 | ELECTRIC - SERVICE UPGRADE | RHOLLAND | Approved | IVRS - Inspection :* 1) GROUNDING ELECTRODE CONDUCTOR NOT TO BE UNDER BACKSIDE OF CLAMPS 2) PLEASE VERIFY GAS AND WATER BONDS 3) A BOND BUSHING IS NEEDED IN METER SOCKET 250.92 4) FILL ALL UNUSED OPENINGS IN PANEL USING APPROVED MEANS. TAPE IS NOT ALLOWED 5) ANTIOXIDE COMPOUND NEEDED FOR ALUMINIUM CONDUCTORS 6) PLEASE VERIFY THIS IS A 125 AMP BUSSED PANEL 7) BACK FEED BREAKER TO USE MANUFACTURERS HOLDOWN 8) WEATHER PROOF COVER, WHETHER OR NOT PLUGGED IN 406.8 9) BOND PANEL ENCLOSURE |
| 09/21/2005 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :* |
| 09/21/2005 | ELECTRIC - CONSTRUCTION POWER | RHOLLAND | Approved | IVRS - Inspection :* |
| 09/21/2005 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection :* |
| 09/21/2005 | ELECTRIC - UNDERGROUND | RHOLLAND | Approved | IVRS - Inspection :* |
| 02/01/2006 | TEP CLEARANCE - AM | JKOZUCH | Approved | INCR |
| 01/31/2007 | PERMIT FINALED | LJACKSON | Approved |