Permit: T05EL01657

Parcel: 111060430

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/22/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
09/21/2005 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1) GROUNDING ELECTRODE CONDUCTOR NOT TO BE UNDER BACKSIDE OF CLAMPS
2) PLEASE VERIFY GAS AND WATER BONDS
3) A BOND BUSHING IS NEEDED IN METER SOCKET 250.92
4) FILL ALL UNUSED OPENINGS IN PANEL USING APPROVED MEANS. TAPE IS NOT ALLOWED
5) ANTIOXIDE COMPOUND NEEDED FOR ALUMINIUM CONDUCTORS
6) PLEASE VERIFY THIS IS A 125 AMP BUSSED PANEL
7) BACK FEED BREAKER TO USE MANUFACTURERS HOLDOWN
8) WEATHER PROOF COVER, WHETHER OR NOT PLUGGED IN 406.8
9) BOND PANEL ENCLOSURE