Permit: T05EL01482
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
718 W SANTA MARIA ST
Address NEW:
718 W SANTA MARIA ST
Apply Date:
07/20/2005
Applicant:
BUCHANAN ELECTRIC INC ,
Description:
UPGRADE: 100-125 AMP
Contractors:
- BUCHANAN ELECTRIC INC ,
Outstanding Activity Conditions
Permit Number - T05EL01482
Permit Status: Expired
Permit Description: UPGRADE: 100-125 AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/20/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T05EL01482
Permite Description: UPGRADE: 100-125 AMP
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2005 | ELECTRIC - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1) 2 GROUND RODS REQUIRED 6' MINIMUM APART 2) BOND GAS PIPING, WATER, TO NEW SERVICE 3) MARKING PEN NOT APPROVED AS ADDRESS LABEL ON SERVICE, MUST BE A PERMANENT LABEL SCREWED OR RIVITED TO ENCLOSURE |
| 08/09/2005 | ELECTRIC - INTERMEDIATE | N/A | Partial Approval | IVRS - Inspection :* 1) NO COMPLIANCE WITH NOTE #2 AND #3 2) BOND GAS PIPING 3) ADDRESS LABEL MUST BE SCREWED OR RIVITED TO COVER 4) OK TO CLEAR INCREASE 5) CALL FOR FINAL AFTER TEP TIE IN-NOTES #2 AND #3 |
Completed Inspections
Permit Status: Expired
Permit Number: T05EL01482
Permit Description: UPGRADE: 100-125 AMP
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/09/2005 | ELECTRIC - UNDERGROUND | DSANTACR | Approved | IVRS - Inspection :* |
| 08/10/2005 | TEP CLEARANCE - AM | HLEYVA | Approved | INC CLEARED BY SANTA CRUZ |